OPzS - Cells

TAB OPzS stationary battery cells are manufactured in the conventional lead-acid battery technology.


OPzS stationary batteries are designed to power telecommunications devices, computers, emergency lighting, alarm, control and monitoring in power plants and distribution stations, at railway stations, airports, etc.

UF_V/Cell1,801,771,751,67EN/IEC 60896-11DimensionsWeightNr.
Discharging time (h)10531RiIscLWHwith aciddryof
TypeAhAhAhAhAmmmmmmkgkgpoles
2 OPzS 1001119785621.48135010320642013.08.02
3 OPzS 150160142122891.08184510320642015.010.02
4 OPzS 2002151871631190.84237610320642017.512.52
5 OPzS 2502682322041490.69288712420642021.515.52
6 OPzS 3003212772421770.5834314520642025.017.02
5 OPzS 3503933362902120.64313712420653629.020.02
6 OPzS 4204704033482540.55364114520653634.024.02
7 OPzS 4905504704062960.48416916620653638.027.02
6 OPzS 6006855825103700.45446614520671146.033.02
7 OPzS 7007986815984360.38528021019170061.041.04
8 OPzS 8009127786834990.33603521019171164.045.04
9 OPzS 90010258757675600.29694821023371174.050.04
10 OPzS 100011409728526220.26772021023371177.055.04
12 OPzS 12001365116510207450.23881421027571191.064.04
12 OPzS 15001645141012208900.238605210275861111.080.04
14 OPzS 175019101640142010350.1910536212397837145.098.06
15 OPzS 187520501760152011100.1811289212397837150.0104.06
16 OPzS 200021851875162511850.1712042212397837154.0109.06
18 OPzS 225024552105182513350.1513506212487837184.0126.08
20 OPzS 250027302340203014800.1315007212487837192.0137.08
22 OPzS 275030002575223016250.1315941212576837222.0149.08
24 OPzS 300032702805243017750.1217390212576837230.0160.08

 

 

 

Electrolyte density: 1,24 ± 0,01kg/l at 20 °C. All measures and weights are within standard production tolerances. Weight tolerance is ± 5 %. Electrical values are approximative. Technical modifications are reserved without prior notice.